Assembly etc.
To be mounted below a ceiling. Remove the front panel. Hold the unit in position and fix it with screws through to back plate. Refit the front panel. Unless requested otherwise, the side slots are locked in a closed position.
Spread pattern
See selection chart for maximum airflow (l/s) for a ceiling mounted unit at 3 °C under temprature and 0.2 m/s velocity at 0.4 m (Y02) distance from the unit.

 

 

Adjustment, cleaning
The unit can be cleaned by removing the front panel. Altering the airflow must be carried out using the external adjustment damper. To achieve the correct air flow and side induction/ impulse pattern, either use an air velocity instrument or smoke gun. The side slots are adjusted to the desired air velocity.
Some of the supply air flow is forced out through the side slots.

Maintenance

Clean with water and a mild detergent solution.


Side slot opening
Open slot (%) / airflow (l/s) at Y02 =0,4m at ΔT 3°C.

LXR 0% 50% 75% 100%
0312 40 50 60 80
0612 110 135 150 170
0618 150 180 200 220
1212 200 230 250 275
1218 260 295 330 365
1224 340 410 450 500

The unit spread pattern can be
altered by adjusting the side
slots.