Assembly etc. |
||||||||||||||||||||||||||||||||||||||||
To be recessed in
a ceiling. Hang the unit so that its flange overlaps the underside of the false ceiling. After the front plate has been screwed in position the that the false ceiling is completed. Unless requested otherwise, the side slots are locked in the closed position.
|
|
Spread pattern
See selection chart for maximum airflow (l/s) for a ceiling
mounted unit at 3°C under temperature and 0.2 m/s velocity at 0.4 m
( Y02) distance from the unit. |
||||||||||||||||||||||||||||||||||||||
|
|
|
|||||||||||||||||||||||||||||||||||||||
Adjustment, cleaning
The unit can be cleaned by removing the front panel.
Altering the airflow must be carried out using the external
adjustment damper.
To achieve the correct air flow and side induction/impulse
pattern, either use an air velocity instrument or smoke gun.
The side slots are adjusted to the desired air velocity. |
Some of the supply
air flow is forced out through the side slots.
|
|||||||||||||||||||||||||||||||||||||||
Maintenance
Clean with water and a mild detergant solution. |
||||||||||||||||||||||||||||||||||||||||
Side slot opening
Open slot (%) / airflow (l/s) at Y02 =0,4m
at ΔT 3°C. |
||||||||||||||||||||||||||||||||||||||||
|
|
||||||||||||||||||||||||||||||||||||||||
|
|
||||||||||||||||||||||||||||||||||||||||
The unit spread pattern can be altered by adjusting the side slots.
|
||||||||||||||||||||||||||||||||||||||||